Depending on the privileges associated with the user, an attacker could then install programs view, change, or delete data or create new accounts with full user rights.

Isagraf workbench code#

Successful exploitation of the most severe of these vulnerabilities could allow for remote code execution.

Isagraf workbench password#

A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device.

isagraf workbench

The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the Tiny Encryption Algorithm (TEA) on an entered or saved password.

  • ISaGRAF Runtime includes the functionality of setting a password that is required to execute privileged commands.
  • This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code.
  • ISaGRAF Runtime searches for and loads DLLs as dynamic libraries.
  • Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. This communication protocol provides various file system operations, as well as the uploading of applications.
  • ISaGRAF Workbench communicates with ISaGRAF Runtime using TCP/IP.
  • A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification.
  • ISaGRAF Runtime stores the password in plaintext in a file that is in the same directory as the executable file.
  • Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution.
  • Some commands used by the ISaGRAF eXchange Layer (IXL) protocol perform various file operations in the file system.
  • Details of these vulnerabilities are as follows: Multiple vulnerabilities have been discovered in Rockwell Automation ISaGRAF5 Runtime which could allow for remote code execution.
  • Large and medium business entities: HIGH.
  • Large and medium government entities: HIGH.
  • Xylem MultiSmart Gen-1 devices and MultiSmart Gen-2 devices running firmware prior to Version 3.2.0 ( If ISaGRAF is enabled on those devices).
  • GE Steam Power's ALSPA S6 MFC3000 and MFC1000 (all versions).
  • isagraf workbench

    Isagraf workbench free#

  • ISaGRAF Free Runtime in ISaGRAF6 Workbench Version 6.6.8 and earlier.
  • AADvance Controller version 1.40 and earlier.
  • isagraf workbench

    There are currently no reports of this vulnerability being exploited in the wild. Successful exploitation of the most severe of these vulnerabilities could allow an attacker to perform remote code execution on the affected device. These affected Industrial Control System (ICS) products are used across several sectors, including chemical, critical manufacturing, food and agriculture, water and wastewater systems and others. Multiple vulnerabilities have been discovered in Rockwell Automation ISaGRAF5 Runtime, the most severe of which could allow for remote code execution. Multiple Vulnerabilities in Rockwell Automation ISaGRAF5 Runtime Could Allow for Remote Code Execution MS-ISAC ADVISORY NUMBER: